Specifications include, but are not limited to: Contractor to provide all engineering, material, and labor including tree-trimming to Engineer,Procure, and Construct (EPC) approximately 3,200ft of a 2-Phase overhead circuit with #2ACSR (Aluminum Cable Steel Reinforced) phase and neutral conductor that was destroyed by atornado.2-Phase Overhead Circuit to be engineered, procure material, and construct.Line Voltage: 12.47kV# of Poles: Approximately 23Conductor Size: #2 ACSR Phase and Neutral.Insulator Type: Porcelain.Pole Classes: Class 3.Tree-Trimming Required.Poles Spans: Approximately 200ft.Lightning Arrestor station: Approximately 1,300ftReplace one 35ft class 4 secondary pole.Fiber glass cross arms Brown PentaA major part of the electrical circuit goes into a wooded area which entails necessary tree-trimming. The original 2-phase circuit contained approximately 23 poles with most of them having received damage caused by high velocity winds.Attached is the Google Earth aerial view image of the Tecumseh property on which the 2-phasecircuit is located. The picture on the left shows the standard image while the one on the right shows lines and symbols which represent the damaged circuit. The white line represents the secondary circuits, the blue represents primary 2-Phase circuit, and the red represents the deer food plot areas.