Specifications include, but are not limited to: 10. FUTURE EQUIPMENT INFORMATION ADDED FOR REFERENCE ONLY. DO NOT USE FOR BIDDING. 9. CHILLER SHALL BE RATED FOR SCHEDULED NOMINAL CAPACITY USING SCHEDULED CONCENTRATION OF PROPYLENE GLYCOL. 8. ENGAGE A MANUFACTURER’S REPRESENTATIVE TO PERFORM STARTUP AND TRAINING SERVICES. IF THE CHILLER WARRANTY IS VOIDED FOR ANY REASON BY THE CONTRACTOR, THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WARRANTY-RELATED REPAIR AND MAINTENANCE COSTS FOR THE LIFE OF THE WARRANTY. 7. CONTROL PANEL SHORT CIRCUIT CAPACITY SHALL MATCH FEEDER KAIC OR PROVIDE WIRING FOR SEPARATE 120V FEED. 6. INSTALL CHILLERS WITH VIBRATION ISOLATION IN ACCORDANCE WITH THE VIBRATION ISOLATION SCHEDULE. G. FACTORY-MOUNTED VARIABLE FREQUENCY DRIVE ON ALL SCREW COMPRESSORS. F. FACTORY-MOUNTED 65KAIC-RATED CONTROL PANEL WITH BACNET CONTROLS TO INTERFACE WITH BAS. REFER TO SEQUENCE OF OPERATION FOR DETAILS. E. EVAPORATOR FLOW SWITCH TO BE FIELD-INSTALLED. D. CONDENSER COIL HAIL GUARDS. C. LOW AMBIENT CONTROLS DOWN TO 0 DEG F. B. INTERNAL SOUND ATTENUATING BLANKET ON COMPRESSORS. A. SINGLE POINT ELECTRICAL CONNECTION WITH NON-FUSED DISCONNECT SWITCH. 5. PROVIDE CHILLERS WITH THE FOLLOWING OPTIONS AND ACCESSORIES: 4. PROVIDE CHILLERS WITH EVAPORATOR FREEZE PROTECTION ON SEPARATE ELECTRICAL CIRCUIT. 3. FOULING FACTOR UNITS ARE CONSISTENT WITH AHRI 550/590: SQ FT x H x DEG F / BTU. 2. ACTUAL CAPACITY (TONS) AND INPUT POWER (KW) ARE BASED UPON THE SCHEDULED CHW TEMPERATURES AND CONDENSER TEMPERATURE. 1