Specifications include, but are not limited to: A 3-pole, twist-lock photocontrol suitable for light emitting diode (LED) lighting fixture applications. Photocontrols shall comply with the requirements of ANSI C136.10 (latest version) and this specification. Construction: Photocontrol shall include a silicon light sensor. Housing shall be encapsulated and made of a long life, impact-resistant material with UV inhibitor and antioxidant additives (sealing per ANSI C136.10, Sec. 4.3) Circuit boards shall have full conformal coating on all sides. Housing Color Shall be Dark Green or Black. Plug Blades shall be solid brass The housing shall indicate the direction that window should be oriented. Date of Manufacture shall be clearly and permanently labeled on each control. Each photocontrol shall be provided with a means to conveniently and permanently record date of installation and date of removal. Electrical: • Nominal operating voltages: 105 to 305 VAC, 60HZ, for operation at 120/208/240/277V. • Operating Temperature: -40C to +70C (-40F to +158F) • Minimum Load Ratings: 1,000W (Incandescent), 1,800VA (HID), 10Amp (Electronic Ballast/LED) • Relay shall be rated for a minimum of 10,000 on/off operations at full load, including an electronic ballast load of 10Amps. • Photocontrol shall be provided with one or more internal surge suppression MOV’s having a minimum combined rating of 640 Joules and meeting the test requirements of ANSI C136.2-2014, including test conditions for the Extreme combination wave test (20kV/10kA). • Power Consumption shall be no greater than 0.5 watts average at 120 VAC • Dielectric Strength shall be per ANSI C136.10 and ANSI C136.2-2015 Operating Characteristics: • Fail Mode: ON • Turn-on: 1.5 FC + or - 0.3 foot-candles (ANSI Std) • The maximum turn-off to turn on ratio shall not exceed 1.5:1 • Time Delay Off: 2 – 6 seconds