Specifications include, but are not limited to: A. CABLES FOR CURRENT TRANSFORMER CIRCUITS SHALL BE FOUR CONDUCTOR SHIELDED, SIZED AS INDICATED ON THE DRAWINGS, AND CONSTRUCTED AS FOLLOWS. 1. CABLE SHALL BE CONSTRUCTED WITH A BARE, ANNEALED COPPER CONDUCTOR, WITH TYPE XHHW-2, UL TYPE TC/TC-ER, MINIMUM 10AWG, 19 STRAND, 600 VOLT, 90°C. PROVIDE A TINNED COPPER TAPE SHIELD FOR 345kV VOLTAGES AND HIGHER. PROVIDE SUITABLE FILLERS IN THE INTERSTICES TO FORM A ROUND CABLE. 2 PROVIDE A UL LISTED SUNLIGHT AND MOISTURE RESISTANT, BLACK, XLPE OR FIRE RETARDANT INSULATION WITH AN OVERALL CPE OR CSPE JACKET. PROVIDE A NYLON RIPCORD IN THE JACKET. JACKET SHALL BE PRINTED WITH REQUIRED UL/NEC INFORMATION AND SEQUENTIAL FOOTAGE MARKINGS. 3. COLOR CODE SHALL BE ICEA S-73-532, METHOD 1 AND TABLE E2 WITH COLORS BEING BLACK (BK), RED (R), BLUE (BL), AND ORANGE (O). 4. CABLE SHALL BE CABLE TRAY RATED AND SHALL MEET ICEA S-73-532. ICEA S-95-658, UL 1277, UL 66, AND UL 83. B. ALL 4/C CONTROL CABLES SHALL BE. SIZED AS INDICATED ON THE DRAWINGS. COLOR CODE SHALL BE ICEA S-73-532, METHOD 1 AND TABLE E2 WITH COLORS BEING BLACK (BK), RED (R), BLUE (BL), ORANGE (O), YELLOW (Y), BROWN (BR), AND RED-BLACK (R/BK). PROVIDE COPPER CONDUCTORS WITH 600 VOLT TYPE XHHW-2 TC RATED, MINIMUM 10AWG, 19 STRAND, 90°C. PROVIDE A TINNED COPPER TAPE SHIELD FOR 345kV VOLTAGES AND HIGHER. PROVIDE SUITABLE FILLERS IN THE INTERSTICES TO FORM A ROUND CABLE. C. ALL 7/C CONTROL CABLES SHALL BE. SIZED AS INDICATED ON THE DRAWINGS. COLOR CODE SHALL BE ICEA S-73-532, METHOD 1 AND TABLE E2 WITH COLORS BEING BLACK (BK), RED (R), BLUE (BL), ORANGE (O), YELLOW (Y), BROWN (BR), AND RED-BLACK (R/BK). PROVIDE COPPER CONDUCTORS WITH 600 VOLT TYPE XHHW-2 TC RATED, MINIMUM 10AWG, 19 STRAND, 90°C. PROVIDE A TINNED COPPER TAPE SHIELD FOR 345kV VOLTAGES AND HIGHER. PROVIDE SUITABLE FILLERS IN THE INTERSTICES TO FORM A ROUND CABLE. D. ALL 12/C CONTROL CABLES SHALL BE SIZED AS INDICATED ON THE DRAWINGS. COLOR CODE SHALL BE ICEA S-73-532, METHOD 1 AND TABLE E2 WITH COLORS BEING BLACK (BK), RED (R), BLUE (BL), ORANGE (O), YELLOW (Y), BROWN (BR), RED-BLACK (R/BK), BLUE-BLACK (BL/BK), ORANGE-BLACK (O/BK), YELLOW-BLACK (Y/BK), BROWN-BLACK (BR/BK), AND BLACK-RED (BK/R), PROVIDE COPPER CONDUCTORS WITH 600V TYPE XHHW-2 TC RATED, MINIMUM 10AWG, 19 STRAND, 90°C. PROVIDE A TINNED COPPER TAPE SHIELD FOR 345kV VOLTAGES AND HIGHER. PROVIDE SUITABLE FILLERS IN THE INTERSTICES TO FORM A ROUND CABLE. E. ALL OTHER CONTROL CABLES SHALL FOLLOW ICEA S-73-532, METHOD 1 AND TABLE E2. ALL CONTROL CABLES SHALL BE COPPER CONDUCTORS WITH 600 VOLT TYPE XHHW-2 TC RATED, MINIMUM 10AWG, 19 STRAND, 90°C. PROVIDE A TINNED COPPER TAPE SHIELD FOR 345kV VOLTAGES AND HIGHER. PROVIDE SUITABLE FILLERS IN THE INTERSTICES TO FORM A ROUND CABLE.