Specifications include, but are not limited to: The selected vendor must be a certified EcoXpert, and a designer of the Schneider Electric family of products branded Invensys, Barber Colman, Siebe, and Robertshaw, and must possess the programming and software tools required to commission and maintain these controllers. Only proposals from authorized suppliers of EcoStruxure will be considered. EcoStruxure Front End Existing SNE Building Systems/Schneider Electric Front End shall remain and the existing software upgraded to the latest revision. All schools shall be seamlessly integrated into the existing front end without the need for a third-party integrator. All new unitary controllers shall be Schneider Electric SmartX MP-C series, MP-V series, and/or RP-C series BACnet/IP controllers (no exceptions). Scope of Work Common to Each School Retain the existing Schneider Electric Automation Server (ASP) and upgrade the software to the latest revision. Remove existing Barber Colman, TAC and Invensys controllers and replace them with new Schneider Electric IP controllers. Retain all existing control end devices and terminate all existing control end device wiring on new controllers. Install new Cat 5/6 control bus daisy-chained between existing Schneider Electric ASP and all new IP controllers. Upgrade existing dynamic color graphics to HTML. Provide all upgrade programming, sequences of operation to match existing and integrate with existing SNE Building Systems/Schneider Electric EcoStruxure Front End. Select balancing for outdoor air and VAV Boxes. Check, Test and Commission all controllers and control devices. Provide a list of any control end devices in need of repair and/or replacement.