Specifications include, but are not limited to: Contractor would install the transmission interconnection facilities (TIF) including new 138kV line terminal equipment at the substation and one 138kV point of interconnection structure outside of the substation. Contractor would construct the new 138kV substation in a breaker and a half arrangement. Contractor would add five (5) 138kV, 3000A, 40kAIC circuit breakers, fifteen (15) 138kV 3000A, Vertical Air Brake switches w/ manual operators, one (1) 138kV 3000A, VAB switch w/ gear operator (A-frame mounted), two (2) single phase 138kV Potential Voltage Transformers, eleven (11) single phase 138kV Potential Transformers, thirteen (13) single phase 138kV 84MCOV Surge Arresters, three (3) Dynasphere air terminals, 4” Sch 80 Aluminum Pipe for 138kV Bus, wire jumpers, ground grid, grounding cu clad conductor, physical security, three (3) 138kV 500:5 metering Current Transformers.