Specifications include, but are not limited to: The Data Center is intended for the rack mounting of computer servers or rack mountable disk arrays. These servers must meet the following general configuration requirements to be rack mounted in the Data Center: o The equipment must be able to be rack mounted in a standard 19” four post rack o Cooling air flow must be from front to back, with cold air entering the front and hot air discharged out the back. o The equipment can be multiple rack-units in height but cannot exceed 39.4 inches in depth o The equipment must have redundant power supplies capable of operating at 208V, up to the available power budget (equipment must be able to run on only A or B power during maintenance) o The equipment must have dual (redundant) network connections to NMT infrastructure (equipment must be able to operate on either network uplink during maintenance) o The equipment must have an installed and functioning out-of-band network management card such as the HP iLO, Dell iDRAC, CMC or SuperMicro IPMI. o User equipment (Networking infrastructure and protocols, plugs, etc.) must be compatible with corresponding data center equipment.