Specifications include, but are not limited to: A. A remote annunciator panel’s monitoring module be used to terminate the new ERCES system with LED lights that monitors power, battery and antenna damage. This panel is typically the first place the Fire/Police Departments review when responding to an emergency call. B. A dedicated 120v power supply with battery backup is required for the new ERCES. The battery back-up shall have a UL 2524 certification. C. The System Integrator (S.I.) shall obtain written approval from the FCC “License Holder”. This License Holder shall be part of the design process since he represents the end user who will provide life safety services to Fire Alarm System Replacement at Carmichael Elementary School. D. The S.I. will need to apply for the end user’s ERCES. This application process serves as both an application & written consent by the applicant and licensee. E. There are currently two types of ERCES. A Class “A” System which is a narrow band device and Class “B” System which is a Broad Band System. The AHJ shall determine which Type of System will be specified.