Specifications include, but are not limited to: Vendor shall furnish and install Industrial Air cleaning Equipment in accordance with these specifications and manufacturer recommendations. Industrial Air cleaner shall be ceiling mounted electric fan belt driven type as manufactured by Air Systems Components Inc. Trion model T2600. To insure compatibility with equipment warranty all installation and secondary components of installation shall be approved or recommended by manufacturer unless otherwise approved by the Town. Ceiling mount and installation by vendor, electrical connections made by the Town. • New air filtration equipment shall be the latest standard production model Trion T2600 Air Boss in compliance with all ANSI and Osha safety requirements and standards. • Unit weight not to exceed 190 lbs. • Blower double squirrel cage with sealed bearings. • Air volume capable of at least 3,000 C.F.M. • Efficiency 95% minimum. • (2) 1” aluminum mesh pre-filters cleanable reusable type. • (2) Spiked Ionizer collector cells Forever type. • Rated for 71 Dba or less. STRUCTURAL - • 45” L X 43” WX 21” H. • Suspended ceiling or wall mounted.