Specifications include, but are not limited to: construction of a drinking water booster pumping station with three (3) pump lines with valves. This contract requires three (3) 1550 gpm pumps with 100 hp motors. A future contract will replace these with three (3) 3350 gpm pumps with 250 HP motors. Work includes providing an extension of RMP power to site. Site requires removing +/-14 feet of collapsible clays below pump station and refilling with structural backfill. Work includes steel and DIP piping, 1 bladder type surge tank; valves (automated and manual), flow meters, fittings and appurtenances; masonry block building with standing seam metal roofing; HVAC system; site work, grading, drainage facilities, asphalt paving, curb and gutter, drain piping, concrete walks, curb and gutter, rock surfacing and revegetation; 24- and 16-inch inlet/outlet DIP pipelines with air valve vaults and connections to existing pipes; electrical, instrumentation, and control systems, standby emergency generator, wiring, telemetry, Owner-provided RTU, chain link fencing, conduits for future electric and controls wiring, and other work.