Specifications include, but are not limited to: 1 - 93PM UPS 80kW 208V or 220V 4 wire in, 208 or 220V 3 or 4 wire out, 80kW Rated, 120kW Frame Capacity, Standard 95% Efficiency, 3 Breaker Sidecar MBS, Includes Power Xpert Gateway Card, Industrial Relay Card, and EMP, Includes 7x24 Startup, and 1 year on-site parts and labor coverage, Power Quality Terms and Conditions apply, PredictPulse Wireless remote monitoring installed during startup, includes 24x7 alarm monitoring, dispatch, reporting, realtime access to health data, LTE cellular modem/router hardware, AT&T Wireless data plan and activation. Qty List of Materials - 1 - 93PM UPS 208V or 220V 4 wire in, 208 or 220V 3 or 4 wire out 120kW UPS Frame, 1 - 93PM IBC-LW Battery Cabinet, 1/1 Cabinets/Strings, 1 - Catalog # CTD93PM 93PM Certified Test Data, 1 - Standard Ground Shipping to FL; 1 Dry Type Transformers Transformer Type: General Purpose Vented - 3 Phase, 112.5 KVA, 1 K-Factor, 480 Primary Volts, 208Y/120 Secondary Volts, Temperature Rise 150C with 220C Insulation System Aluminum Winding Material, Sound Reduction : 0, NEMA ST-20 Audible Sound Level: 50, Efficiency : DOE 10 CFR Part 431 (2016), UL Listed : Y, Enclosure Type: NEMA 2 (for N3R, select Weather Shield in Mods tab), Operating Frequency: 60 HZ