Specifications include, but are not limited to: • Provide 60’ x 40’ enclosed light weight metal structure with a vertical roof and 12’ eaves. Per attached Building layout. • Basis of design is a Handi-House light steel storage building. • Building is to meet state minimum wind rating for its intended location. • Building legs are be minimum 4' on center. • 24 Gauge minimum on building panels. • Roll up door are to be 10’ x 10’ Laundry storage side insulated door. • Provide 4" steel Sch 40 painted bollards with caps on both sides of each roll up doors. • Provide motorized continues duty exhaust fan on cart side of building. • Provide 208/120-volt, single phase 200-amp service, 36-circuit service rated Square D panel (or equal) with Main Breaker and all required breakers. • Provide underground service conduit and conductors from panel up to weather head on utility pole approximately 85’ from building location. Underground conduit to be PVC and exterior conduit above ground to be GRC. (sized per NEC). Provide and install electrical meter can on utility pole.