Specifications include, but are not limited to: Weatherproof equipment, including but not limited to resistance to rain, wind, and flooding – Cabinet/Enclosure rating of NEMA 3R (min) • Mounting Options: Pedestal mount or Free-Standing • Modularity – Unit shall be able to be modularly expandable or connected to additional units in the future for integrated build-out of DC Fast Charging infrastructure at the RWRA facility • Use of high quality and visually attractive materials that complement and enhance the existing RWRA facility locations (2101 Grimes Ave, Owensboro, KY 42303) • Compliance with National Electrical Code, FCC, UL Rated, Energy Star Rated and other relevant regulations for safety and operation • Compliance with the Americans with Disabilities Act (ADA) • Max Output Power: 120kW • Voltage: 150 – 1000Vdc • Power (kVA): 480 (3ph + N + PE) + 10% • Frequency: 60 Hz • DC Connector Type: CCS-1 (or NACS with provided CCS-1 Adapter) • Cable Length: 25 ft • Cable Management System: Yes • Cable Locking Mechanism: Yes • Connector Configurations: 2x 60kW simultaneously, 1x 120kw sequentially • Maximum Continuous Current CCS [A]: 200A Connector (300A Connector - optional) • Peak Current CCS [A]: 350A • Protections Isolation monitor • Optional De-Rate • Fully networked to allow for the management of charging operations including access, power distribution, and charging notifications – Wi-Fi and Ethernet capable • Data Protocol: OCPP 1.6 • Screen display(s) shall be user-friendly and easy to operate. Displays shall be LCD, LED or equivalent, and shall be readable in direct sunlight and at night • Cabinet visual Indicators (Lights) indicating: Ready for Charge, Fast Charging, Slow Charging, Fault or Standby modes (min) • Security design that is both tamper-proof and vandalism-proof, such as tamper-resistant screws, antivandalism hardware, locked enclosures, and graffiti-resistant coating