Specifications include, but are not limited to: Generator Specifications: • Arena o Make: Cummins o Model: DFLC-5567296 o S/N: I020415711 o Size: 1250kW o ATS Qty: 5 • Convention Center o Make: Cummins o Model: DFGB-5567298 o S/N: I020418320 o Size: 600kW o ATS Qty: 3 Repairs and Installation needed: 1) De-energize generator and connect rented backup generator. a. Rented generator needs to be 600KW – Make: Cat, Model: XQ600 2) Remove obsolete generator control and annunciator. 3) Pull out existing cabling in conduits going outside to generators and from cable tray to annunciator panels to make room for new cables. 4) Install 1-Belden 9729 cable and 1-2 conductor 14-gauge stranded cable. Successful Bidder will be responsible for field measurements. For bidding purposes, use the measurements listed below: a. Arena - 500’ of cable b. Convention - 1000’ of cable 5) Install new generator control (Cummins 3X control) and annunciator (Cummins Universal annunciator). 6) Disconnect backup generators and hook MECA’s generators back up. 7) Test to make sure everything works. Option MECA is interested in receiving pricing on a monitoring solution that is capable of providing alerts via text messaging, email, app notification, etc. regarding start-ups and errors. Please include pricing on the proposal form and submit detailed specifications with your bid for any options that are available for our consideration. Details should include any hardware, software, licensing, etc. that are required for use of the proposed solution.