Specifications include, but are not limited to: The Contractor shall provide, on a semiannual basis, all labor and material and supervision for an Inspection & Testing service as specified herein for Fire Alarm System.C. The Contractor shall furnish all labor, materials, any batteries, and supervision required to determine the operational status of each device of the existing Fire Alarm System(s). Inspection & Testing service procedures provided by contractor shall conform to NFPA standards as adopted by 675 of the Indiana Administrative Code. D. The minimum number of planned inspection cycles shall be two (2) times per fiscal year spaced approximately 180 days apart and shall conform to required testing frequencies as tabulated within NFPA 72 for each fire alarm component type. The first Inspection & Test cycle shall be performed upon successfully being awarded the contract. E. Each Inspection & Test site visit shall be prescheduled and directed from a maintenance management program initiated and maintained by the Contractor. The program shall be either computer directed or manually operated. A copy of this schedule shall be in the hands of the Physical Plant Director prior to the start of any work. F. All work shall be performed in the presence of an Agency Representative who shall sign the job ticket documenting that the work is complete. The signatures of those performing the work shall appear on all work orders or job tickets.