Specifications include, but are not limited to: A. Contractorshallperform work at Old State House Museum and their ancillary buildings located at300 West Markham Street, Little Rock, Arkansas.B. Contractorshallremove existing 2,100 MBH boiler andshallinstall a new 1,999 MBH or higherefficiency boiler.C. Contractorshallremove existing class B vent for existing boiler and water heater.D. Contractorshallinstall new vent. New ventmustbe rated for condensing boilers.E. Contractorshallremove existing water heater andshallinstall new 40-gallon water heater.F. Contractorshallremove existing pump andshallinstall new 5 HP heating water pump.G. Contractorshallrework obstructive sections of existing heating and chilled water piping to allowproper access to the equipment.H. Contractorshalladd a primary heating water pump andshallconvert pumping system to avariable flow system.I.Contractorshalladd an outside air temperature sensor to allow for heating water temperaturesetback for energy conservation.