Specifications include, but are not limited to: A. Category 6 Cable installations to support Wireless Local Area Network 1. Install additional category 6 cable to existing WAP and label from Wiring Enclosure in Room 380 to the following locations 1. Room 379 2. Room 380 2. Install and label category 6 cable from Wiring Enclosure in Room 212 to the following locations 1. Library a. One additional line to the existing WAP b. Two lines to each of the far corners of the library near the Exit signs 2. Cafeteria a. One additional line to the existing WAP b. Two lines to the opposite side of the Cafeteria 3. Install and label category 6 cable from Wiring Closet in Room 1A to the following locations 1. Auditorium a. One additional line to the existing WAP b. Two lines to each of the front corners of the Auditorium near the Exit signs B. All installations shall be installed, labelled, tested and certified to the applicable ANSI/TIA/EIA-568-B.2 standards and a copy provided to NCSU/NCUHS C. Provide a 1-year Warranty/Guarantee of equipment from the date of project completion/acceptance by NCSU/NCUHS D. All work must be completed and satisfactorily tested before July 31, 2018.