36C241-25-AP-4384 Newington Replacement Breakers Q and A Can you please advise part # of breaker needed / pictures of existing breaker? There are 2 breakers noted in the solicitation. The first of which cannot be racked out for information due to the support bracket being damaged. This is the breaker that needs to be replaced. Here is the information I have available to me: MFR: EATON Catalog # MDN4083XEA0552N Frame Type: K600-AR-600NM Frame Size: 800 Voltage Rating: 480 Trip Unit: DIGITRIP 520 Trip Rating: 250 Can you please send us the catalog number for this breaker and information on the trip unit? If you have any pictures, that would help. The second breaker failed a trip test and will need the trip unit replaced. Here is the information I have available from the second breaker. MFR: EATON Catalog # MDN4083XEA0552N Frame Type: K600-AR-600NM Frame Size: 800 Voltage Rating: 480 Trip Unit: DIGITRIP 520 Trip Rating: NA (This will need to be dialed in as best you can) Please note as stated in the SOW, this breaker will need a temporary unit for use until the trip unit is rebuilt, and the breaker can be racked back in. This unit supports the hospital s CT scanners and downtime is not acceptable. Please also note that each breaker will require a testing report via secondary injection testing to verify functionality.