Solicitation 89503425QWA001006 -LETCHER, SD MATERIAL
 
Amendment 00002 incorporates the following:
 
Adds question and answer section:
 
 
 - QUESTION:  The specification sheets provided in Amendment 1 indicate the conductor is to be tinned copper braid shielded.  However, in recent years WAPA has been specifying corrugated copper tape for shielded 5/C #10 and 12/C #10 conductor.  Please clarify shielding for 5/C #10 and 12/C #10 conductor.  3/C #8 is often non-shielded.  Please confirm that tinned copper braid shielded is required for the 3/C #8.
ANSWER:  WAPA wants the copper braid shielded not the taped. No shielding needed on the 3/C #8.
 
 
2. QUESTION:  Manufacturer is requesting details regarding items 12 – 18 on the list of items requested.  Please confirm if these are VNTC or portable cables.
 
Answer:  These would be VNTC for the ones it applies to 16, 17, and 18.
 
 
A signed copy of this amendment must accompany your quote to be considered.