Specifications include, but are not limited to: Building Interior Size 26'-5" L x 14'-10" W x (By Vendor) H (approx.) Shipping Split Quantity Not Specified. Determined by Contractor. Aisle Width Not Specified. Determined by Contractor. Floor Load 250 psf Roof Load 80 psf Wind Load 120 mph Seismic Design Category A Wall System IMP with inner and outer walls of 26 ga. Steel and inner foam barrier. Aisle Doorways One (1) 4' W x 8' H, One (1) 3.5' W x 7' H External Ground Pads Four (4) NEMA drilled (one at each corner) HVAC Not Specified. Sizing determined by Contractor per Section 26 13 26. DC Battery System C&D 60 cell 3DJC-05HP Battery Rack C&D 2-tier RDB0801-7.3P Battery Charger La Marche A12B, 15A DC, 130V DC, 120V 60Hz AC Eye Wash Station One (1) Fendall 1000 or equiv. (w/ Saline Solution) Battery Spill Containment System Required. Fire Extinguisher Required. Hydrogen Detector Required. Hydrogen Exhaust Fan Required. AC Panel One (1) 225A, 120/240 single phase, 42 position NEMA 1 panel. 200A main breaker. DC Panel One (1) 225A, 125V DC, 42 position NEMA 1 panel. 200A main breaker. DC Disconnect Switch One (1) 200A, 125V DC, NEMA 1 Switch. AC Manual Transfer Switch One (1) 225A, 120/240 single phase, NEMA 1 Switch, Non-Fusible. Breaker Test Cabinet Required. Lighting Contactor Required with dusk-to-dawn photocell. Four (4) spare positions required. Door Panic Bar Required. Door Lock Required. Door Contact Switch Required. Enclosure Temperature Alarm Required. File Cabinet Required. Finish ANSI 61 gray exterior and white interior