Specifications include, but are not limited to: Supply, design, fabrication, galvanizing, and delivery of lightning masts and anchors for three new substations. Substation Lightning Masts for B Street, E. 7th Street and WEC station o All anchor bolts and setting templates for all structures o Design of tapered tubular lightning masts o Foundation reactions for lightning masts ; The scope of supply shall include materials, fabrication, and testing for substation wide flange and small tubular steel structures. Small tubular steel structures are those structures fabricated with common structural tubing or pipe listed in the AISC "Manual of Steel Construction." All structural steel material shall meet the criteria specified on the Specification Data Sheet(s) in accordance with the standard Charpy "V" notch impact test. The Charpy test shall be in accordance with ASTM A370 and ASTM A673/A673M. The Charpy test shall be made on a heat lot basis. Certified mill reports of the mechanical and chemical properties of materials shall be submitted to the Owner for review. Certified copies of embrittlement test reports performed in accordance with ASTM A143 shall be submitted to the Owner for review.