Specifications include, but are not limited to: 1. The following electrical service entrance equipment (photos on page 2, item 13) shall be replaced in-kind per HECO’s Electric Service Installation Manual, 9th Edition: a. Service Mast, including but not limited to the weatherhead, conduit riser, and HECO’s messenger anchoring accessories (insulator and hardware) for attaching the utility service drop at the customer’s mast. b. Sealable NEMA 3R wireway above the meter socket/main breaker enclosure c. Enclosed NEMA 3R meter socket/main breaker for HECO meters numbers 827023 and 827025 i. Provide a new main breaker for each installation matching the existing trip and AIC ratings ii. Disconnect and reconnect the existing load side feeder to the main breaker 2. Examine site and electrical service entrance equipment for size and rating of equipment, enclosure types and wiring. a. Provide an electrical single line sketch with proposal. 3. Coordinate with HECO to perform the repairs. Reference can be made to the notice of deficiency, Attachment A, when contacting HECO. 4. The interior lights are non-functional. Test the existing interior light system, up to 6 switch and light fixture circuit, and replace, in-kind, non-operational circuit breakers, light switches and wiring as required to make the lighting circuit functional. 5. Remove and properly dispose of 4 existing ceiling surface mounted interior lights.