Specifications include, but are not limited to: 600 AMP Panelboard & Electric Circuit Breaker; Ref: ReliaGear RD 600AMP Panel 2 Section(s), Nema 1 Enclosure 600 Amps, 3 Phase 3 Wire 480V, 50/60 Hz Minimum Interrupt Rating: 22kA Fully Rated Section 1 of 2 Incoming Feed: Bottom Surface Mounted 36 Circuits UL67 / CSA C22.2 No. 29 Certified cULus Certified Approximate Dimensions: 64.5” H x 20” W x 5.75” D o The depth of the panel must be between 5.50” and 6.25” 600 Amps Main Lugs 1-lug/phase 2-cable/lug 2/0 -500 kcmil Main Option Details Feed Thru Lugs Aluminum Bus Heat Rated Ground-Box bonded(2) TGL2 Ground main lug(2) TGL20 NEMA 1 Enclosure Feeders (12) Breaker Device 50 Amps 3 Poles FBVTE Modifications Same Box Size Power Distribution Panel Interior: ADF3366MBX AXT1 Box: AB64B Front: AF64S Section 2 of 2 Incoming Feed: Top Surface Mounted 36 Circuits UL67 / CSA C22.2 No. 29 Certified cULus Certified Approximate Dimensions: 64.5” H x 20” W x 5.75” D o The depth of the panel must be between 5.50” and 6.25” 600 Amps Main Lugs 1-lug/phase 2-cable/lug 2/0 -500 kcmil Main Option Details Aluminum Bus Heat Rated Ground-Box bonded(2) TGL2 Ground main lug(2) TGL20 NEMA 1 Enclosure Feeders (8) Breaker Device 15 Amps 3 Poles FBVTE (4) Breaker Device 50 Amps 3 Poles FBVTE Modifications Same Box Size Power Distribution Panel Interior: ADF3366MT Box: AB64B Front: AF64S