Specifications include, but are not limited to: The West Virginia Purchasing Division is soliciting bids on behalf of the WV Department of Administration, General Services Division ("GSD," "Owner," or "Agency") to establish a contract for qualified contractors to perform Cooling Tower rehabilitation/ construction services located at the Central Plant aka Bldg 11, 218 California Avenue, Charleston, West Virginia 25311; 1.1.1. Remove 100% of the fill in (3) cells of Towers 3 thru 5 and place in Contractor supplied dumpsters for removal-Contractor responsible for debris removal. State retains salvage of metal/motors/etc. for recycling upon removal will be turned over to the West Virginia General Services Division. 1.1.2. With fill removed mechanically prepare the leaking end walls to a SSPC-SP-10 or NACE No. 2 Near White Blast surface finish to achieve a minimum 3mil. surface profile and coat with CIM Industries 1061 (or equal) two component elastomeric urethane coating to a thickness of 60 wet mils. 1.1.3. Supply and install new Brentwood Industries or equal bottom supported heavy duty XF75 15mil fill packs. To include: 1.1.3.1. XF 75 15mil. thickness after forming packs with integrated louvers and integrated drift eliminators. 1.1.3.2. Fill material installed at 64” of air travel to match the existing air travel. 1.1.3.2.1. New FRP corrosion resistant fill supports. FRP material to be supplied from a US based supplier. 1.1.3.3. New FRP/PVC/Neoprene corrosion resistant air and water seals. 1.1.4. Remove and replace mechanical components in (3) cells, to include: 1.1.4.1. (3) New Marley (or equal) fans selected Marley HP7i composite/fiberglass airfoil blade to meet or exceed the original OEM, includes all new hub housing. 1.1.4.2. (3) New two speed motors 75/18.75hp. 1800/900 RPM, 460V, 405T. 1.1.4.3. (3) New OEM Marley or equal 27001 gear reducers.