Specifications include, but are not limited to: Bid work includes all (Plumbing, HVAC & Electrical & General Construction work) work necessary to install a complete and working Chiller Replacement as shown on the plans. 1. Provide Microprocessor controlled, multiple scroll compressor, air-cooled, liquid chillers of the scheduled capacities as shown and indicated on the Drawings, including but not limited to: a. Chiller package b. Charge of refrigerant and oil c. Electrical power and control connections d. Chilled liquid connections e. Manufacturer start-up C. QUALITY ASSURANCE 1. Products shall be Designed, Tested, Rated and Certified in accordance with, and Installed in compliance with applicable sections of the following Standards and Codes: a. AHRI 550/590 – Water Chilling Packages Using the Vapor Compression Cycle b. AHRI 370 – Sound Rating of Large Outdoor Refrigerating and Air-Conditioning Equipment c. ANSI/ASHRAE 15 – Safety Code for Mechanical Refrigeration d. ANSI/ASHRAE 34 – Number Designation and Safety Classification of Refrigerants e. ASHRAE 90.1 – Energy Standard for Buildings Except Low-Rise Residential Buildings f. ANSI/NFPA 70 – National Electrical Code (N.E.C.) g. ASME Boiler and Pressure Vessel Code, Section VIII, Division 1 h. OSHA – Occupational Safety and Health Act i. Manufactured in facility registered to ISO 9001 j. Conform to Intertek Testing Services for construction of chillers and provide ETL/cETL Listed Mark 2. Factory Run Test: Chiller shall be pressure-tested, evacuated and fully charged with refrigerant and oil, and shall be factory operational run tested with water flowing through the vessel. 3. Chiller manufacturer shall have a factory trained and supported service organization.