Specifications include, but are not limited to: PART 2 – SCOPE OF WORK 1. Replace Panel in Sally Port Electrical closet with same amperage bolt in style, ground fault rating and Breaker spacing. 2. Remove all unused circuits. 3. All panels and disconnects will be inspected for proper termination of wiring and conduits. Replace and Repair as needed. 4. Remove old wiring from new records retention area and replace with code compliant installation for current use of area. (copper thhn installed in metal conduit) 5. Remove old HVAC control box’s and associated wiring located in electrical room. 6. Remove all unused automated door control wiring. 7. Remove all unused intercom wiring. 8. Remove Door and Intercom cabinets. 9. Remove unused data and Audio Video cables. 10. Replace data cables that are not terminated at both ends with cat 6. 11. Insure all data is operational. 12. Run new circuits for the new multipurpose room. (Per Drawings) 13. Replace missing or none working lights. (Led fixtures provided) 14. Remove smoke evacuation switch gear. 15. Rewire Exhaust and supply fan for evidence room. 16. Remove and or repair outlets, switches and circuitry in old dispatch room. 17. All emergency circuits will be marked with red on conduits and or Junction Boxes. 18. All receptacles on emergency circuits will be red in color. 19. All circuits existing and new circuits and outlets will be marked with lettering and numbering to identify panel and breaker