Specifications include, but are not limited to: The Project consists of replacement of the existing HVAC systems controls with new DDC controls and installation of advanced meters.; TEMPERATURE CONTROLS: A. Provide a complete and operating fully integrated Building Control System (BCS) of electronic digitally processed energy management, temperature controls and monitoring for the building air distribution system, air conditioning systems, rooftop conditioning units, heating fluid systems, exhaust fans, unit heaters, pumps and other equipment and systems included as part of the work for this Division.; B. The BCS shall be comprised of a series of Automated Logic WebCNTRL® BACnet™ compliant digital controllers and sensors and an Ethernet LAN interface with complete control and energy management system administrative software for web based user interface and operation of the control network. User access shall only require the use of generic internet browser software on the client PC with password access and security level control.; C. Control system shall have a complete, fully functional user interface accessible through a standard web browser for complete monitoring and user operation of the energy management and control system functions. Building shall be under control of the building operators through a web interface.; D. Electric controls and mechanical devices for all items indicated on drawings, required for implementation of the operating sequences and as described hereafter including electronics, valves, wiring, interface devices and panels.; E. A communications network to allow data exchange from each electronic controller to each other, controllers to user interface units and to the existing user interface personal computer.: 1. The controller level communication network shall be an HVAC industry standard open protocol fully compliant with the BACnet™ standard and technology.; 2. The local BCS network to web interface and communication network shall be provided and utilize the Owner’s existing local area network.; F. Installation, check out and calibration of all control devices and systems including existing HVAC control devices scheduled for continued operation under this work.; G. Provide controller programming to allow standalone operation of each unit controller. All points utilized for operation of one mechanical unit must reside in one dedicated controller. Provide all report programming, graphics development and schedule integration for a Web Server gateway that shall provide user access to this system.; H. Provide all software tools for installation, operation and adjustment of control programs and electronic controller resident firmware settings. Install on the Owner's PC or notebook PC.