Specifications include, but are not limited to: Installing a, emergency back-up generator at the DMVA, Hangar 6 at JBER, Alaska.; A. Work under this Contract includes all design, material, permits, tools, labor and travel, if necessary, to complete the project detailed herein and located at building 47430 in Bryant Army Airfield, JBER, Alaska. All work must be completed in accordance with the terms and conditions of the Contract Documents.; B. The work at the National Guard Armory includes designing and providing in complete and perfect working order a new diesel fuel fired standby generator system to supply power to the entire armory building, as seen in the attached map. The contractor shall provide all materials, appurtenances, and labor to provide for a standby power system that will automatically start and transfer from normal power to standby power upon a power failure and shut off when power is restored.; C. Contractor must comply with all applicable Federal, State, and Local Regulations and Requirements including but not limited to; Unified Facilities Criteria (UFC), OSHA, NEC, and NFPA. 1. The Standby Generator System is to be designed by a Professional Electrical Engineer, licensed to work in the State of Alaska and submitted for approval to the project manager.; 2. Generator sizing to be based on Appendix D of UFC 3-540-01, 1 Aug 2014 with Change 2, 5 Nov 2019.; 3. Generator and pad placement, and all trenching shall be limited to within the earmarked area indicated in the attached generator layout.