Specifications include, but are not limited to: MSB-P 800 A MAIN FUSIBLE SWITCH 120/208 V 3P 4W WYE NEMA 1 FULLY RATED 65,000 AIC BUS BRACING 65,000 AIC DEVICE MIN INT RATING COPPER BUS COPPER GROUND BUS MAIN SECTION TOP HAT – 18” H DISTRIBUTION SECTION DUAL RATED AL/CU LUGS DIMENSIONS - 90” H X 90” W X 24” D FRONT LINEUP – LEFT TO RIGHT DISTRIBUTION SECTION – 51” W MAIN SECTION – 39” W TOP HAT THIS SECTION ONLY TOP HAT TO BE REMOVABLE REMOVE SYSTEM BONDING JUMPER LOCATED PRUCHA HALL ROOM 13 BASED ON AMP CUSTOM SWITCHBOARD (4) 200/3 (6) 100/3 (2) 60/3 (2) 200/3 SPARE SWITCHES; MSB-S 800 A MAIN LUG ONLY 120/208 V 3P 4W WYE NEMA 1 FULLY RATED 65,000 AIC BUS BRACING 65,000 AIC DEVICE MIN INT RATING COPPER BUS COPPER GROUND BUS TERMINATION SECTION DISTRIBUTION SECTIONS DUAL RATED AL/CU LUGS TOP HAT AS INDICATED – 18” H DIMENSIONS - 90” H X 102” W X 24” D FRONT LINEUP – LEFT TO RIGHT DISTRIBUTION SECTION – 39” W TOP HAT THIS SECTION ONLY TOP HAT TO BE REMOVEABLE TOP HAT W/ SPLIT FRONT COVER DISTRIBUTION SECTION – 39” W TERMINATION SECTION – 24” W REMOVE SYSTEM BONDING JUMPER LOCATED STRATTON HALL ROOM 1A BASED ON AMP CUSTOM SWITCHBOARD (11) 200/3 (6) 100/3 (2) 60/3 (1) 200/3 SPARE SWITCH.