Specifications include, but are not limited to: Replace the generator at the Lower Church Street Pump Station. The generator will provide power to operate a section of our wastewater system. Generator: One (1) Generac SD030 Diesel Generator, 2.2 Liter I4 Turbocharged Diesel Engine, 1800 RPM, 120/208 Volt Three Phase, H100 Digital Controls, 1500W 120VAC Block Heater, 12 Volt Starting Batteries, 10 A Battery Charger, 125 Amp Main Line Circuit Breaker, Sound Attenuated Enclosure, Remote Mounted Emergency Stop, 132 Gallon Double Wall Base Tank (47 Hour Run Time), Standard 2- year limited warranty, with one year maintenance agreement. Transfer Switch: One (1) Generac 200 AMP TX Automatic Transfer Switch, rated 200 amps, three pole construction, 120/208 Volt Three Phase, NEMA 3R Enclosure.