Specifications include, but are not limited to: The UPS system shall include the following options and accessories: A. Integrated Maintenance Bypass, Distribution, Parallel Tie and Accessory Cabinet(s): Integrated Line-and-Match cabinet(s) shall be provided that include(s): 1. All hardware and interconnecting cable for connection to UPS module. 2. Three-breaker manual maintenance bypass switch in a sidecar configuration, to isolate UPS module from commercial AC input and critical load. The sidecar may be mounted on either side of the UPS module. Switch shall provide complete isolation of UPS for servicing. Switch shall be make-before-break, interlocked between UPS and bypass to prohibit improper operation. B. Network Adapter and UPS Power Monitoring Software: PX Gateway card adapter shall provide a communications interface between the UPS module and the following network management systems. 1. SNMP v.1, v.3 2. Modbus TCP 3. BACnet/WS or /IP 4. IPv6 This capability shall allow the unit to be monitored remotely over an Ethernet network using a standard web browser. C. UPS Power Monitoring Software: This system shall continuously monitor critical power elements associated with the UPS, using the communications port on each module and a customer furnished PC. The system shall automatically alarm if any problems arise and notify local or remote personnel of the alarm condition via email, page, or text message. D. Relay Card: Serial dry contact card providing 4 isolated dry output contacts, 1 isolated input. The relays are programmable. E. External Battery Cabinet(s): The battery cabinet shall feature valve regulated, high-rate discharge, lead-acid batteries which provide energy to the support the critical load during a momentary loss of input power to the rectifier. The batteries shall be flame retardant in accordance with UL 94V2 requirements. The battery cabinet shall have the following features: 1. The battery cabinet shall be the same depth and height as the UPS module. 2. The battery cabinet shall feature a mechanical enclosure of like appearance to the UPS module and shall feature casters for easy installation. Each battery cabinet shall require front access only for installation, service and maintenance. The battery cabinet shall provide bottom cable entry standard and top entry capability via sidecar. 3. Power wiring internal to each battery cabinet shall be factory provided. Each battery cabinet shall feature up to 10 battery trays which can be individually disconnected from the battery cabinet power wiring with quick disconnect devices. Each battery tray shall be firmly secured to the battery cabinet frame with fasteners. Each battery tray shall be removable from the front of the battery cabinet. 4. Each battery cabinet shall feature a DC rated circuit breaker. The circuit breaker within the battery cabinet shall only provide protection to the battery string(s)