Specifications include, but are not limited to: A. Provide new engine generator system consisting of all required equipment, sensors, conduit, boxes, wiring, piping, supports, accessories, system programming, etc. as necessary for a complete operating system that provides the functional intent indicated. B. Provide products listed, classified, and labeled as suitable for the purpose intended. C. System Description: 1. Application: Emergency/standby. 2. Configuration: Single packaged engine generator set operated independently (not in parallel). D. Packaged Engine Generator Set: 1. Type: Diesel (compression ignition). 2. Power Rating: a. As required by the manufacturer to power (1) 20 HP, 208V, three phase, VFD-controlled sewage pump with a base load of 5 kW of miscellaneous resistive load, within the specified voltage and frequency tolerances, but not less than 30 kW/37.5 kVA at 0.8 power factor, standby. 3. Voltage: a. 208Y/120 V, 3 phase, 60 Hz. The neutral shall not be bonded to ground at the generator. 4. Main Line Circuit Breaker: a. Type: Thermal magnetic.