Specifications include, but are not limited to: A. Lubricating System 1. First inspection change oil and filters annually (all new filters will be marked with installation date) 2. Approximately 180 days after first inspection, perform complete oil analysis and provide written report to Physical Plant Director, within 14 days after inspection. 3. Lubricate all fittings. 4. Check and report all leaks. B. Fuel System 1. Change fuel filters elements annually. 2. Check generator set for fuel leaks. 3. Adjust and clean injectors annually. 5. Check operation of fuel transfer pump and check for leaks. 6. Check float switch on day tank. 7. Inspect Main Tank/Day tank fuel levels. 8. Inspect and test all pressure regulators on propane, natural gas fueled units. 9. Inspect governor linkage. 10. Visually Inspect containment basin. 11. Where fuel oil being used, Once per year perform a basic fuel analysis with results and interpretations of results provided to the Facilities manager within 14 days of the sample being taken. Basic fuel test to consist of the following items: Sulfur Content, Biodiesel Content, Karl Fischer Water, Particle Count, Elemental Analysis, Microbial Growth, Visual Inspection.