Specifications include, but are not limited to: Fire Alarm & Detection System Service Number of Inspections per Year: 1 Month Inspection is Due: June ➢ Perform sensitivity test every 2 years. ➢ Check fire alarm panel to ensure that the alarm initiating devices are functioning properly. ➢ Verify the alarm indicating devices are functioning properly. ➢ Verify that the supervisory/trouble signal initiating devices are functioning properly. ➢ Verify system primary and auxiliary power supplies including battery backups are sufficient. ➢ Functionally test detectors with test smoke. ➢ Pull every pull station and check their accessibility. ➢ If the facility has a remote annunciator, verify that the points being monitored are correct. ➢ If the system is monitored, verify the signal reached the monitoring company. Backflows Number of Inspections per Year: 1 Month Inspection is Due: June ** Parts & Labor for identified needed repairs will be quoted and invoiced in (1) additional PO. ➢ Test backflow preventers inspected by certified backflow technicians. ➢ Submit Results to governing entities for certification. Hood Inspections Number of Inspections per Year: 2 Month Inspection is Due: June + December ➢ Test and Inspection service per industry standards. ➢ Semiannual Discharge and actuation piping verification. ➢ Replacement of all fusible links. ➢ Replacement of gaskets (On Ansul Systems). ➢ Replacement of all rubber blow off caps annually (Ansul). ➢ Replacement of Pilot cartridge on Pyro Chem, Range Guard, and Buckeye systems. ➢ Use of test links. ➢ All Service Fees per Schedule of Values