Specifications include, but are not limited to: E1 INSTALL NEW PANEL. PROVIDE AND INSTALL 200A, 120/208V, 30 CIRCUIT PANEL [1]. RUN NEW WIRE THROUGH EXISTING 2" RIDGID METAL CONDUIT ALONG THE SIDE OF THE BLEACHERS WALL BACK TO NEW FUSED 200A DISCONNECT LOCATED UNDER THE SOUTH ENDZONE BLEACHERS. SEE SHEET 1/E2 FOR LOCATION OF NEW 200A DISCONNECT AND CONNECTION CONTINUATION. COORDINATE WITH ATHLETIC DEPARTMENT FOR EXACT LOCATION OF PANEL MOUNTING. SEE PANEL SCHEDULES FOR HOW BREAKERS SHOULD BE CIRCUITED. E2 INSTALL OWNER PROVIDED PANEL. REUSE CONDUIT AND WIRE FOR THIS PANEL. EXISTING PANEL FED FROM EXISTING DISTRIBUTION PANEL 'DP-1'. E9 INSTALL FOUR NEW 5-20R RECEPTACLES. CONNECT TO NEW 200A, 120/208V PANEL 'FE1' LOCATED EAST OF THE 50 YARD LINE. EACH RECEPTACLE WILL BE ON ITS OWN DEDICATED CIRCUIT. SEE DIAGRAM 3/E1 FOR HOW TO LINE RECEPTACLES UP. E10 REWIRE EIGHT EXISTING RECEPTACLES TO NEW 200A, 120/208V PANEL 'FE1' LOCATED EAST OF THE 50 YARD LINE. EACH RECEPTACLE WILL BE ON ITS OWN DEDICATED CIRCUIT. E11 INSTALL SIX NEW 5-20R RECEPTACLES. CONNECT TO NEW 200A, 120/208V PANEL 'FW1' LOCATED WEST OF THE 50 YARD LINE. EACH RECEPTACLE WILL BE ON ITS OWN DEDICATED CIRCUIT. SEE DIAGRAM 3/E1 FOR HOW TO LINE RECEPTACLES UP. E12 REWIRE SIX EXISTING RECEPTACLES TO NEW 200A, 120/208V PANEL 'FW1' LOCATED WEST OF THE 50 YARD LINE. EACH RECEPTACLE WILL BE ON ITS OWN DEDICATED CIRCUIT. E13 INSTALL NEW 2" RIGID METAL CONDUIT BETWEEN EXISTING JUNCTION BOXES TO ALLOW WIRE TO BE PULLED FOR NEW PANELS AS NOTED IN CONSTRUCTION NOTE E1.