Specifications include, but are not limited to: The Contractor shall provide all labor, equipment, crane, materials and insurance necessary to remove the existing Public Works Administration generator and transfer switch and replace it with a Cummins C200D6d, Diesel Genset, 60Hz, 200kW generator, a OTECSED, OTEC Service Entrance Transfer Switch-Electronic Control: 800A/1000A, a kit enclosure, and a kit fuel system as well as removing the existing Municipal Building generator and transfer switch and replace it with a Cummins C60N6, Standby, Natural Gas Genset, 60Hz, 60kW generator, a OTCEB, OTEC Transfer Switch-Electronic Control: 150A/225A/260A, a sound level 2 Baffle, and all necessary work to complete installation per the attached equipment specifications labeled as Exhibit “B”. 1.2 New generators and transfer switches shall be manufactured by Cummins. No other manufacture will be accepted. 1.3 Include extended comprehensive warranty of 5 years 2500 hour to include parts, labor, and travel for generators and transfer switches. 1.4 Start up and commissioning shall be performed by Cummins authorized representative. 1.5 4 hour Load Bank shall be performed by Cummins authorized representative. 1.6 4 hour owner training shall be performed by Cummins authorized representative. 1.7 Existing diesel fuel shall be filter and transfer into new tank. 1.8 Sound level 2 required for both generators.