Specifications include, but are not limited to: Removal and disposal of existing generator by the Town of Swanzey.; Existing three phase circuit powering siren installed in adjacent structure, Mt. Caesar Library, to be removed; Full electrical installation of generator, 3 panel upgrades, automatic transfer switch and installation of 8 space 16 circuit sub panel.; Connection from generator to auxiliary fuel tank (Auxiliary tank to be supplied by the Town of Swanzey).; Engine battery and carburetor heater.; Generator will be located in existing bunker.; One Blue Star, 30kw, 120/208 Volt, 1800 RPM, Diesel Fueled Standby Generator with 70 Gallon Fuel Tank Generator will serve essential circuits up to 30,000 watts to include lighting, computer and radio equipment, garage door openers, boiler, fire alarm, water heater and well pump and exhaust capture system.; One ASCO, 104 Amp, 120/208 Volt, Automatic Transfer Switch in Sound Attenuated Enclosure or approved equal.; Factory warranty startup and owner training session.; Required permits and inspections by the Town of Swanzey.