Specifications include, but are not limited to: 10. REFER TO ARCHITECTURAL WALL ELEVATIONS FOR PLACEMENT OF DEVICES (TEMPERATURE SENSORS, MANOMETERS, ETC.). WHERE DEVICES ARE NOT SHOWN IN ARCHITECTURAL PLANS, COORDINATE WALL SENSOR LOCATIONS WITH ARCHITECTURAL PLANS AND ELEVATIONS TO AVOID CONFLICTS WITH CASEWORK, WALL PANELS, ETC. DO NOT INSTALL SENSORS BEHIND DOOR SWINGS.; 11. COORDINATE THE LOCATION OF ROOF & WALL PENETRATIONS WITH STRUCTURAL ELEMENTS. PROVIDE AT NEW WALL PENETRATIONS SLEEVES 1" LARGER IN DIAMETER THAN THE PIPE INSULATION & EXTENDING 1-1/2" BEYOND FINISHED SURFACES. FILL ANNULAR SPACE WITH FIRESTOPPING INSULATION & CAULK.; 12. WHERE THE INTERIOR SURFACE OF DUCTWORK IS VISIBLE FROM AN OCCUPIED SPACE, THE VISIBLE SURFACE SHALL BE PAINTED MATTE BLACK.; 13. CONTRACTOR SHALL LOCATE ALL EQUIPMENT ABOVE CEILING (E.G. TERMINAL UNIT) IN PLAN & ELEVATION TO ALLOW SUFFICIENT ACCESS FOR PROPER MAINTENANCE & SERVICE OF EQUIPMENT.; 14. ALL HVAC SYSTEMS SHALL BE ENERGIZED, TESTED, ADJUSTED & BALANCED AS SPECIFIED.; 15. ACCESS PANELS ARE REQUIRED IN GYPSUM BOARD CEILINGS FOR ALL VALVES, TRAPS, DAMPERS, CLEANOUTS, CONTROLS, EQUIPMENT, ETC. & SHALL BE FURNISHED AND INSTALLED IN ACCORDANCE WITH THE ARCHITECTURAL SPECIFICATIONS.; 16. PROVIDE REMOTE DAMPER REGULATOR, AS SPECIFIED, FOR EACH VOLUME DAMPER LOCATED ABOVE AN INACCESSIBLE CEILING. REFER TO ARCHITECTURAL RCP SHEETS.; 17. ROUTE PIPING TO TERMINAL UNITS TO AVOID CLEARANCE AREAS FOR ACCESS PANELS, CONTROLS ENCLOSURES, ETC.; 18. ALL HYDRONIC PIPE RUNOUTS TO TERMINAL UNITS SHALL BE 3/4" U.N.O.