Specifications include, but are not limited to: two (2) primary substation, liquid filled transformer as required for complete and operating systems, and as specified herein. The transformer shall ship as a complete, fully-assembled unit requiring no parts to be installed in the field by the Owner or installing contractor. All freight is to be included. The transformers shall be identified as follows: 1. One (1) Health Science South Substation Transformer HSS-XFMR-1 2. One (1) Health Science South Substation Transformer HSS-XFMR-2 The ratings of the transformer shall be as follows: kVA Rating: 5000/5600/6250/7000 ONAN/ONAF Impedance: 6.5% nominal at base MVA, ANSI standard tolerance Losses: Manufacturer Standard HV: 22.9kV Delta HV BIL: 150kV HV De-energized Taps: +/- 2 - 2-1/2% full capacity,DETC LV: 4360Y/2517 Volts Wye LV BIL: 75kV LV Tap Changer: See description below Altitude: 3,300 feet or less