Specifications include, but are not limited to: (1) Design. a) Review the number and location of existing Fire Alarm System devices and confirm that such quantity and locations are compliant with all applicable governing regulations. Note previously classified hazardous locations, as identified on the legacy Design Drawings (Exhibit B. North WWTP – Existing Electrical Drawings and Exhibit C. East WWTP – Existing Electrical Drawings). b) Identify all changes in the number and location of Fire Alarm System devices that are required to achieve a fully compliant Fire Alarm System. c) Furnish, install and/or relocate any Fire Alarm System devices to achieve a fully compliant Fire Alarm System including, but not limited to, fire alarm pulls to achieve American Disability Act (ADA) compliance (see Exhibit D. North WWTP – Existing Fire Alarm System Device Tabulation and Exhibit E. East WWTP – Existing Fire Alarm System Device Tabulation). d) Review the requirement for fire alarm and detection system devices in the basement of the valve house at the North WWTP. Upgrade or eliminate system devices as appropriate. e) Select specific replacement Fire Alarm System devises including, but not limited to; detectors, modules, switches, pull stations, horns and strobes. A listing of acceptable devices is provided within the referenced technical specification (Exhibit A. Specification Section 13850 – Fire Alarm System). f) Confirm that all selected devices are appropriate for the intended installed purpose and shall result in a fully compliant Fire Alarm System.