Specifications include, but are not limited to: Camp Washington Carver: Replacement of Fire Alarm Panel; 2.1 ALARM-INDICATING DEVICE A. (Add Alternate #1) NEMA 4X exterior, weather -resistant Strobe Light and Horn Device: 1. Strobe (Color: RED): a. LED, NEOBE™ type flashing light minimum 75 flashes per minute OR, b. Xenon 1.75 joule energy flash, minimum 50 ECP (effective candle power).60-80 flashes per minute 2. Horn Output: Minimum, 90 db @ 10 Feet. B. Central Fire Alarm Control Panel: Non-proprietary Central fire alarm panel (i.e., Honeywell, Edwards, Siemens, & etc.) with a minimum of Fifty (50) device connection points compatible with existing Alarm Indicating Devices (i.e., Pull Stations, Strobes, horns, Smoke and/or heat detectors, &etc.) and monitoring circuits (i.e., Fire Suppression Systems, Range Hoods & etc.) and a charging circuit for Sealed Lead Acid storage batteries. UL 864- – Standard for Safety for Control Units and Accessories for Fire Alarm Systems.