Specifications include, but are not limited to: The three new pumps (chilled water, heating water, and condenser water) will be installed in the existing mechanical room. ; (1) Chilled Water Horizontal End Suction Pump 1. Total Flow: 430 gpm 2. Chilled Water Total Head: 125 ft 3. Minimum Efficiency: 70% 4. Motor HP: 25 5. Motor RPM: 1800 6. Motor Voltage and Phase: 460 / 3 (1) Heating Water Horizontal End Suction Pump 1. Total Flow: 230 gpm 2. Heating Water Total Head: 90 ft 3. Minimum Efficiency: 70% 4. Motor HP: 10 5. Motor RPM: 1800 6. Motor Voltage and Phase: 460 / 3 (1) Condenser Water Horizontal End Suction Pump 1. Total Flow: 540 gpm 2. Heating Water Total Head: 30 ft 3. Minimum Efficiency: 75% 4. Motor HP: 7.5 5. Motor RPM: 1800 6. Motor Voltage and Phase: 460 / 3