Specifications include, but are not limited to: Power Supply (New) Provide a new power supply to include 3 phase, 4 wire system with a ground wire and a single phase supply for elevator lighting. Coordinate with Building Personnel for proper routing, and tie in with existing building 3 phase power. Provide fused lockable disconnects for both 3 phase and single phase circuits inside machine room, as close to machine room entrance as possible. Travel Cables (NEW) The existing traveling cables will be replaced. All traveling cables will be new and properly suspended between car and hoistway or machine room cable support. All cables will incorporate the specified types of conductors. At a minimum, each traveling cable will contain one shielded and jacketed pair. Cables will be supported by steel supporting strands if travel exceeds 150 feet and in a loop compatible to size of cable. The outer covering will be fire resistance and meet Underwriters Laboratories standard test. The cables will be hung free of all contact from hoistway or car equipment. Cables will contain adequate number of conductors to provide a minimum of 10% of spares.