Specifications include, but are not limited to: 1 New Generator 275kW –Equivalent to: Kohler 120/208V, three-phase, pad mount generator with block heater, battery, battery charger and remote annunciator to replace existing 260 kw Cummings generator To include:•One (1) new Kohler 600A automatic transfer switch (ATS)•Disposal of existing generator and ATS unit•Rework existing generator feeder, block heater circuit, battery charger circuit and control wiring from new generator to new ATS unit. Include associated conduits/wiring as required.•Deliver, offloading and rigging to remove existing generator and set new generator.•100 gal fuel for startup, testing and training •Start –up, testing, commissioning and owner training.•Permits and inspections$ $ $ 1 New Generator 180kW –Equivalent to: Kohler 120/208V, three-phase, pad mount generator with block heater, battery, battery charger and remote annunciator to replace existing 180 kw Cummings generator To include:•Disposal of existing generator •Rework existing generator feeder for new generator.•Deliver, offloading and rigging to remove existing generator and set new generator.•Existing generator pad to be re-used for new generator.•Existing 600A Asco transfer switch (ATS unit) to be re-used.•Provide rewire of existing ATS unit, block heater, battery charger and ATS wiring for new generator.