Specifications include, but are not limited to: Steel Tank: Remove the existing interior and exterior lead-based coatings from a 1.0 million gallon, 66-foot diameter steel water tank. Provide containment and abatement of leadbased paint on tank interior and exterior. Weld areas of corrosion on interior tank components. Apply new high performance interior and exterior coating. Install new safety ladder and standing platform for access to roof. Install Cathodic Protection system, including magnesium anodes on tank floor. Miscellaneous electrical and mechanical improvements. Install Owner Furnished Equipment which includes submersible mixers and all necessary appurtenances to bring mixers into full operation. Concrete Tank: Remove and replace the exterior coatings from the roof of an 82-foot diameter concrete water tank. Miscellaneous electrical and mechanical improvements. Remove existing deteriorated hatch hardware and replace with owner furnished stainless steel hardware. Install Owner Furnished Equipment which includes submersible mixers and all necessary appurtenances to bring mixers into full operation.