Specifications include, but are not limited to: a.Check Wiring for shorts, opens, resistance to ground b.Check end of line resistor, diode, or capacitorc.Test all manual stationsd.Calibrate smoke detectors: Sensitivity checked 100% year 1, 0% year 2 and 100% year 3. Heat detectors to be checked 20% per FA panel per year FYI: so at the end of 5 years 100% will be checked.e.Test all signals – horns, bells, chimes, lights, strobes, and speakersf.Test Zone and remote annunciationg.Test zone coding and pre-signalsh.Test local and remote trouble signalsi.Test fan shut downj.Test Elevator recallk.Test batteriesl.Present owner with Fire Alarm Test Report per each of the three building groups as described above; 1.) Academic (AC) 2.) Housing (HS) and 3.) Coyote Student Center (CSC). Vendor to keep additional copies of all inspection records for the three building types.m.Report to owner all malfunctions and service requirements at the end of each building.