Specifications include, but are not limited to: The CO2 Feed System equipment and services to be provided by the Supplier shall include the following: 1. Remote fill station, including the fill connection (as required by Supplier), isolative valve(s), tank level display, stainless steel weather enclosure and any other required appurtenances. Supplier shall connect to the Type 304 SS CO2 feed pipe using a 1-1/2” stainless steel flange. Supplier shall make electrical connections to an aluminum junction box adjacent to the fill station containing three 2/C#16TPS cables for communications with the feed system. For details, see attached Bidding Documents for the separate construction contract. 2. 14-ton vertical, cylindrical carbon steel CO2 storage tank. Maximum diameter for the storage tank shall be 8’-0”. Tank shall be installed on a reinforced concrete pad provided under the separate construction contract. 3. Chemical Feed System consisting of dual evaporators and associated control valves and appurtenances to provide redundancy. Each evaporator shall be capable of supplying an average of 500 lbs/day of CO2 and a maximum flow of 1500 lbs/day. A manual bypass arrangement with rotometer shall be provided for use in the event automatic control is lost. 4. Interconnecting stainless steel piping between equipment on the storage tank pad. See attached Bidding Documents for the separate construction contract for locations and sizes of connection points.