Specifications include, but are not limited to: Fire alarm testing shall be performed as specified. During each inspection, all control equipment shall be checked for proper operation. All of the peripheral devices (smoke detectors, pull stations, etc.) and their associated annunciators shall be tested for proper response to alarm and trouble conditions. During each inspection, all of the peripheral devices shall be tested. At the completion of the tests, all control equipment shall have been tested, and each individual peripheral device shall have been tested once. Additionally, during each annual test, at least one device from each and every circuit shall be tested in order to ensure that all circuits are functioning. Bi-annual testing is limited to substations. Complete testing documentation shall be presented for each location, either in Microsoft Word or Excel spreadsheet format, as specified below.