Specifications include, but are not limited to:This work is providing and installing the components of the lighting and electric system for the new building as shown on the Drawings. This work includes trenching for U.G. electric from existing pole or pad to new building as well as installing a 200 amp panel and installation of the telephone and data lines from the office to the mechanical room and office. A. Circuit Panel Box — The circuit panel box shall be dead front design complying with NEMA PB 1 and be circuit breaker type. Panel-board bus shall be copper with copper ground bus. The enclosure shall be NEMA PB 1, Type 1 with a surface type cabinet front, screw fastened cover with hinged door and flush lock. Finish color is standard gray enamel. Provide a 40-space minimum panel box (200-amp service) for the new building. Acceptable manufacturers are Siemens, Cutler-Hammer, Square-D or General Electric. No Homeline will be accepted. B. Circuit Breakers — The circuit breakers are molded case circuit breakers conforming to NEMA AB 1, stab lock design. Circuit breakers must be equipped with integral thermal and instantaneous magnetic trip in each pole. Provide circuit breakers UL listed as Type SWD for lighting circuits. Do not use tandem circuit breakers. Acceptable manufacturers shall be Siemens, Cutler-Hammer. Square-D or General Electric. No Homeline will be accepted. C. Wire — Romex type NM-B AWG #6 through #12 wire with ground. Wire must be in conduit where exposed. D. Outlet and Junction Boxes — Metal or PVC for surface mounting only in the heated bay and outside of the building. Provide closures for unused ports and waterproof covers for outside receptacle boxes. PVC “New Work” boxes can be used in walls