Specifications include, but are not limited to: ● UPS systems must be compatible with APC Powerchute Business Edition for remote network monitoring, and support (at a minimum) these protocols: SNMP, SMTP, NTP ● UPS systems at MDF locations must support at minimum: 5kVA load, 208v AC, NEMA L6-30 input/output connectors, and 1-hour runtime at 50% load ● UPS systems at IDF locations must support at minimum: 1500VA, 120v AC, NEMA 5-15 input/output connectors, 15 minutes runtime at 50% load ● All UPS systems must be rack mountable ● All equipment must be in new condition. No refurbished or used equipment will be accepted. ● UPS systems must support commonly available field replaceable batteries ● Vendor must provide the quantities of UPSes with the further specifications listed below.